| FXUA50AVEB | FXUA71AVEB | FXUA100AVEB | FXUA50AVMB (Archived) (Preliminary) | FXUA71AVMB (Archived) (Preliminary) | FXUA100AVMB (Archived) (Preliminary) | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Heating | At high fan speed | dBA | 37.0 | 40.0 | 47.0 | 37 | 40.0 | 47.0 | |
| At low fan speed | dBA | 33.0 | 36.0 | 40.0 | 33 | 36.0 | 40.0 | |||
| At medium fan speed | dBA | 35.0 | 38.0 | 44.0 | 35 | 38.0 | 44.0 | |||
| Cooling | At low fan speed | dBA | 33.0 | 36.0 | 40.0 | 33 | 36.0 | 40.0 | ||
| At high fan speed | dBA | 37.0 | 40.0 | 47.0 | 37 | 40.0 | 47.0 | |||
| At medium fan speed | dBA | 35.0 | 38.0 | 44.0 | 35 | 38.0 | 44.0 | |||
| Refrigerant | GWP | 675 | 675 | 675 | 675 | 675 | 675 | |||
| Type | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | ||||
| Power input - 50Hz | Cooling | At high fan speed | kW | 0.029 | 0.055 | 0.117 | 0.050 | 0.090 | 0.200 | |
| Heating | At high fan speed | kW | 0.029 | 0.055 | 0.117 | |||||
| Cooling capacity | Total capacity | At high fan speed | kW | 5.6 | 8.0 | 11.2 | 5.6 | 8.0 | 11.2 | |
| Nom. | kW | 5.6 | 8.0 | 11.2 | ||||||
| Piping connections | Liquid | OD | mm | 6.4 | 6.4 | 9.5 | 6.35 | 6.35 | 9.52 | |
| Type | Flare connection | Flare connection | Flare connection | |||||||
| Gas | OD | mm | 12.7 | 12.7 | 15.9 | 12.7 | 12.7 | 12.9 | ||
| Type | Flare connection | Flare connection | Flare connection | |||||||
| Drain | VP20 | VP20 | VP20 | I.D. 20/O.D. 26 | I.D. 20/O.D. 26 | I.D. 20/O.D. 26 | ||||
| Sound power level | Cooling | At high fan speed | dBA | 55.0 | 58.0 | 65.0 | 55 | 58 | 65 | |
| Air filter | Type | Resin net | Resin net | Resin net | Resin net with mold resistance | Resin net with mold resistance | Resin net with mold resistance | |||
| Dimensions | Unit | Width | mm | 950 | 950 | 950 | 950 | 950 | 950 | |
| Depth | mm | 950 | 950 | 950 | 950 | 950 | 950 | |||
| Height | mm | 198 | 198 | 198 | 198 | 198 | 198 | |||
| Casing | Material | Resin | Resin | Resin | Resin | Resin | Resin | |||
| Colour | Fresh White | Fresh White | Fresh White | |||||||
| Weight | Unit | kg | 27 | 27 | 28 | 26 | 26 | 27 | ||
| Fan | Air flow rate - 50Hz | Cooling | At high fan speed | m³/min | 17.0 | 22.5 | 31.0 | 17 | 22.5 | 31.0 |
| At low fan speed | m³/min | 13.0 | 16.0 | 21.0 | 13 | 16.0 | 21.0 | |||
| Heating capacity | Total capacity | At high fan speed | kW | 6.3 | 9.0 | 12.5 | 6.3 | 9.0 | 12.5 | |
| Nom. | kW | 6.3 | 9.0 | 12.5 | ||||||
| Current - 50Hz | Maximum fuse amps (MFA) | A | 6 | 6 | 6 | 16 | 16 | 16 | ||
| Power supply | Phase | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | |||
| Frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | |||
| Voltage | V | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220-230 | 220-240/220-230 | 220-240/220-230 | |||
| Notes | (1) - Contains fluorinated greenhouse gases | (1) - Contains fluorinated greenhouse gases | (1) - Contains fluorinated greenhouse gases | |||||||
| Standard Accessories | Thermal insulation tube | 3 | 3 | 3 | ||||||
| Sealing material | 4 | 4 | 4 | |||||||
| Wire clamp material | 10 | 10 | 10 | |||||||
| Drain hose | 1 | 1 | 1 | |||||||
| Hose band | 1 | 1 | 1 | |||||||
| Drain joint | 1 | 1 | 1 | |||||||
| Washer fixing plate | 1 | 1 | 1 | |||||||
| Extension auxiliary pipe | 1 | 1 | 1 | |||||||
| Non woven fabric | 1 | 1 | 1 | |||||||
| Screws | 5 | 5 | 5 | |||||||
| Washer | 8 | 8 | 8 | |||||||
| Notes | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | |||||||
| (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | ||||||||
| (3) - The sound power level is an absolute value indicating the power which a sound source generates. | (3) - The sound power level is an absolute value indicating the power which a sound source generates. | (3) - The sound power level is an absolute value indicating the power which a sound source generates. | ||||||||
| (4) - Instead of a fuse, use a circuit breaker | (4) - Instead of a fuse, use a circuit breaker | (4) - Instead of a fuse, use a circuit breaker | ||||||||
| (5) - Select wire size based on the value of MCA | (5) - Select wire size based on the value of MCA | (5) - Select wire size based on the value of MCA | ||||||||
| (6) - Contains fluorinated greenhouse gases | (6) - Contains fluorinated greenhouse gases | (6) - Contains fluorinated greenhouse gases | ||||||||