Specifications Table for EWYQ-ADVP

EWYQ005ADVP EWYQ006ADVP EWYQ007ADVP
Sound pressure level Heating Nom. dBA 50 (5)
  Cooling Nom. dBA 50 (5)
Hydraulic components Expansion vessel Volume l 6
Refrigerant charge Per circuit kg 1.70
  Refrigerant charge-=-Per circuit-=-TCO2Eq TCO2Eq 3.55
Compressor Type   Hermetically sealed swing compressor
  Starting method   Inverter driven
  Quantity   1
Weight Operation weight kg 104
  Unit kg 100
Air heat exchanger Type   Tube type
EER 2.72 (1) 2.53 (1) 2.39 (1)
Refrigerant GWP   2,087.5
  Type   R-410A
  Circuits Quantity   1.00
  Control   Inverter
Cooling capacity Nom. kW 5.28 (1)
Piping connections Water heat exchanger drain   5/16 SAE flare
Water heat exchanger Minimum water volume in the system l 10
  Type   Brazed plate
  Water flow rate Min. l/min 12
Power input Cooling Nom. kW 1.94 (1)
  Heating Nom. kW 1.65 (2), 2.02 (3)
Sound power level Cooling Nom. dBA 62.0
COP 3.65 (2), 2.76 (3)
Dimensions Unit Width mm 1,190
    Depth mm 360
    Height mm 805
Capacity control Method   Inverter controlled
Heating capacity Nom. kW 6.02 (2), 5.57 (3)
Water circuit Piping connections diameter inch 1" MBSP
Power supply Phase   1~
  Name   V3
  Frequency Hz 50
  Voltage V 230
Notes (1) - Tamb 35°C - LWE 7°C (DT=5°C) (1) - Tamb 35°C - LWE 7°C (DT=5°C) (1) - Tamb 35°C - LWE 7°C (DT=5°C)
  (2) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C) (2) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C) (2) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
  (3) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (3) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (3) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
  (4) - Including piping + PHE; excluding expansion vessel (4) - Including piping + PHE; excluding expansion vessel (4) - Including piping + PHE; excluding expansion vessel
  (5) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. (5) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. (5) - The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.
  (6) - Contains fluorinated greenhouse gases
Cooling capacity Nom. kW   6.08 (1) 7.18 (1)
Capacity control Method     Inverter controlled Inverter controlled
Power input Cooling Nom. kW   2.40 (1) 3.00 (1)
Dimensions Unit Depth mm   360 360
    Height mm   805 805
    Width mm   1190 1190
Weight Operation weight kg   104 104
  Unit kg   100 100
Casing Colour     Ivory white Ivory white
  Material     Polyester painted galvanised steel plate Polyester painted galvanised steel plate
Fan Quantity     1 1
  Type     Propeller fan Propeller fan
Compressor Quantity     1 1
  Type     Hermetically sealed swing compressor Hermetically sealed swing compressor
  Starting method     Inverter driven Inverter driven
Operation range Air side Cooling Min. °CDB   10 10
      Max. °CDB   43 43
  Water side Evaporator Min. °CDB   5.00 5.00
      Max. °CDB   20 20
Sound power level Cooling Nom. dBA   62.0 63.0
Sound pressure level Cooling Nom. dBA   50 (5) 50 (5)
Refrigerant GWP     2087.5 2087.5
  Circuits Quantity     1.00 1.00
Power supply Frequency Hz   50 50
  Voltage range Min. %   -10 -10
    Max. %   10 10
Unit Running current Max A   19.0 19.0