Specifications Table for ERA-AY

ERA100A7Y1B ERA125A7Y1B ERA140A7Y1B
Cooling capacity Nom. 35°CDB kW 12.1 (1) 14 15.5 (1)
Heating capacity Nom. 6°CWB kW 12.1 (2) 14 15.5 (2)
SEER 7.9 (3) 7.4 (3) 7.3 (3)
SCOP 4.9 (3) 4.5 (3) 4.5 (3)
Indoor index connection Min.   63 100 100
  Max.   100 125 140
Dimensions Unit Height mm 869 869 869
    Width mm 1100 1100 1100
    Depth mm 460 460 460
Weight Unit kg 102 102 102
Fan External static pressure Max. Pa 45 45 45
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor
Operation range Cooling Min. °CDB -5 -5 -5
    Max. °CDB 46 46 46
  Heating Min. °CWB -20 -20 -20
    Max. °CWB 15.5 15.5 15.5
Sound power level Cooling Nom. dBA 67 68.1 (4) 69
Sound pressure level Cooling Nom. dBA 49 51 51
Refrigerant Type   R-32 R-32 R-32
  GWP   675 675 675
  Charge tCO2Eq 2.3 2.3 2.3
  Charge kg 3.4 3.4 3.4
Piping connections Liquid Type   Braze connection Braze connection Braze connection
    OD mm 9.52 9.52 9.52
  Gas Type   Braze connection Braze connection Braze connection
    OD mm 15.9 15.9 15.9
  Total piping length System Actual m 50 (6) 50 (6) 50 (6)
  Level difference OU - IU Outdoor unit in highest position m 50 50 50
      Indoor unit in highest position m 40 40 40
Standard Accessories Auxiliary piping set 1 1 1
  Installation and operation manual 1 1 1
Power supply Name   Y1 Y1 Y1
  Phase   3N~ 3N~ 3N~
  Frequency Hz 50 50 50
  Voltage V 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications.
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (11) - TOCA means the total value of each OC set. (11) - TOCA means the total value of each OC set. (11) - TOCA means the total value of each OC set.
  (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan
  (13) - For AHU HEX volume limitations, refer to the engineering data book or installation manual (13) - For AHU HEX volume limitations, refer to the engineering data book or installation manual (13) - For AHU HEX volume limitations, refer to the engineering data book or installation manual
  (14) - For detailed contents of standard accessories, see installation/operation manual (14) - For detailed contents of standard accessories, see installation/operation manual (14) - For detailed contents of standard accessories, see installation/operation manual